Pump chamber repair · Camberley area, Surrey

Flooded junction box and failed floats near Camberley

Alton Pumps attended an overflowing manhole near Camberley. The engineer found rotten float cables, two floats not working and a junction box full of water. The junction box was replaced and the chamber was working in automatic.

Project completed September 2025

Open junction box with orange and white connectors beside pump chamber cables
The junction box and its connectors.

The visit

The visit was to install a new junction box and to investigate an overflowing manhole.

What was found

The float cables inside the tank were rotten. The wire snaps inside the insulation when the cables are stripped back. Two floats, the assist float and the high-level float, were not working because of water getting in. The junction box inside the tank was full of water.

Two cable ends with exposed wires held in a gloved hand
Cable ends checked during the visit.

What was done

The junction box was replaced and the chamber was working in automatic.

Gloved hands wiring connectors in an open junction box
Wiring the replacement junction box.

Position at the end of the visit

At the end of the visit the chamber was running off only one float, and had no high-level float working.

Pump chamber seen from above with lifting chains and a junction box on the wall
The pump chamber.

Recorded outcome

  • Faults found: rotten float cables, two floats not working and a junction box full of water.
  • Repair: the junction box was replaced.
  • Result: the chamber was working in automatic.
  • Still outstanding: the chamber ran off one float, with no high-level float working.

This case study is written from the completed job record. Photographs are from the job. Customer names and addresses are not published.

About this job

What was found in the chamber?

Rotten float cables, two floats not working because water had got in, and a junction box full of water.

What was repaired?

The junction box was replaced and the chamber was working in automatic.

Was everything fixed?

At the end of the visit the chamber ran off only one float and had no working high-level float.