Pump station call-out · Warsash, near Southampton

Tree roots in a pump station near Warsash

A road pumping station near Warsash had one pump out of action and an automatic mode that was not working reliably. Alton Pumps found the chamber full of roots with the floats caught, cleared the roots and reported a fault in the control panel.

Project completed November 2025

Tree roots hanging inside a pump chamber beside a lifting chain
Roots filling the pump chamber.

The call

The customer reported problems with their road's pumping station. One pump seemed to be out of action, and the automatic mode on the second pump was not working reliably.

What was found

The chamber was very heavily rooted, and the floats were caught in the roots.

Chamber cover lifted showing roots and cobwebs inside a pump chamber
The chamber with its cover lifted.

What was done

The engineer removed all the roots and checked that the floats operated. The pumps were lifted and checked, and were fine. The system was left in auto.

Submersible pump lifted out of a chamber on its lifting chain
A pump lifted from the chamber for checking.

The control panel

The panel looks to have had a small fire inside it, or its capacitors have blown. The switch relay is not working and needs replacing as soon as possible. The engineer also advised a good wash down of the chamber.

Marks on a rail inside a pump control panel
Marks inside the control panel.

Recorded outcome

  • Cause found: roots filling the chamber and catching the floats.
  • Roots removed: and the floats checked.
  • Pumps checked: both were lifted and found fine.
  • Panel fault reported: the switch relay is not working and needs replacing as soon as possible.

This case study is written from the completed job record. Photographs are from the job. Customer names and addresses are not published.

About this job

Why was the automatic mode unreliable?

The chamber was heavily rooted and the floats were caught in the roots.

Were the pumps faulty?

No. The pumps were lifted and checked, and were fine.

What else needed doing?

The switch relay in the control panel was not working and needed replacing as soon as possible. A wash down of the chamber was also advised.